What information do I need to provide?
For a full and accurate SAP Assessment you will need to provide the following;
- Location Plan
- Floor Plans
- Elevations
- Sections (a section is required for each variation of the proposed dwelling).
- Technical Specification (This will be indicative and RTS will amend and design specifications in order to achieve compliance).
Current U-Values - New Thermal Elements
| Element type | Maximum U-value(1) W/(m2·K) |
|---|---|
| Roof | 0.15 |
| Wall | 0.18 |
| Floor | 0.18 |
| Swimming pool basin | 0.25 |
| Window | 1.4 or Window Energy Rating(10) Band B minimum |
| Rooflight | 2.2 |
| Doors with >60% of internal face glazed | 1.4 or Doorset Energy Rating(10) Band C minimum |
| Other doors | 1.4 or Doorset Energy Rating(10) Band B minimum |
Current U-values - Existing Thermal Elements
| (a) U-value Threshold | (b) U-value Improved |
|---|---|
| Roof: 0.35 | 0.16 |
| Wall - cavity insulation: 0.7 | 0.55 |
| Wall - internal or external insulation: 0.7 | 0.3 |
| Floor: 0.7 | 0.25 |
If existing thermal elements achieve a U-value equal to or lower than threshold (a) then no upgrading will be required, however, if the U-valiue is above threshold A then the element will need to be improved to the U-value in column (b).